R290 Green
The hansetherm R290 Green is your entry into the top class and is unparalleled in terms of performance, energy efficiency and economy. With the hansetherm R290 Green, we rely on state-of-the-art compressors from HIGHLY and on the natural refrigerant R290.
Your advantages at a glance
- R290 refrigerant
- ErP class A+++ / A+++
- Compressor from HIGHLY
- Circulation pump from Grundfos
- Inverter technology
- 5 years warranty
- Galvanized, corrosion-free housing
- Low noise operation
- Elegant, screwless shaft design
hansetherm R290 Green (Air-Water Heat Pump)
The built-in circulation pump from Grundfos is characterized by particularly low-vibration, maintenance-free and extremely durable operation.
Thanks to the monoblock design, the R290 Green requires very little floor space and is installed completely outside. Even at an outside temperature of -25°C, the heat pump still operates very reliably. Another advantage is also the sound-optimized design. Thus, the sound pressure level corresponds to only 43 dB(A) at a distance of 1 m. The hansetherm R290 Green can be integrated into an existing heating system or used as a stand-alone heat generator. This gives you complete flexibility.
hansetherm products stand for quality and durability. Therefore, we give you from the day of installation or purchase – 5 years that your unit is free from manufacturing defects. This manufacturer’s warranty only applies to devices installed in Germany by a recognized specialist trade company
Certificates
hansetherm R290 Green (Air-Water Heat Pump)
Model |
HT-R290G-8-B |
HT-R290G-14-B |
HT-R290G-14-S |
HT-R290G-22-B |
HT-R290G-22-S |
|
Power Supply |
/ |
230V~/50Hz |
230V~/50Hz |
380~415V/3N~/50Hz |
230V~/50Hz |
380~415V/3N~/50Hz |
Moisture Resistance |
IPX |
IPX4 |
IPX4 |
IPX4 |
IPX4 |
IPX4 |
Electrical Shockproof |
I |
I |
I |
I |
I |
I |
Heating Conditions |
|
|||||
Heating Capacity Range |
kW |
2.53~9.58 |
5.56~16.82 |
5.40~14.95 |
8.76~24.55 |
8.75~24.55 |
Heating Power Input Range |
kW |
1.79~2.82 |
3.26~5.12 |
5.56~16.82 |
4.79~7.25 |
4.95~7.25 |
Heating Current Input Range |
A |
2.9~9.2 |
4.6~16.9 |
1.9~6.8 |
7.0~30.3 |
2.8~12.2 |
Heating Power at A7/W35 |
kW |
7,8 |
13,7 |
13,7 |
20 |
20 |
Heating Power at A2/W35 |
kW |
6,35 |
11,8 |
11,8 |
16,8 |
16,85 |
Heating Power at A-7/W35 |
kW |
5,5 |
10,3 |
10,31 |
15 |
15,08 |
Heating Power at A-7/W55 |
kW |
4,38 |
8,2 |
8,2 |
12,62 |
12,63 |
COP A2/W35 |
|
3,38 |
3,32 |
3,32 |
3,32 |
3,34 |
COP A7/W35 |
|
4,08 |
3,83 |
3,83 |
3,92 |
3,92 |
Cooling Conditions |
Ambient Temperature (T/F): 35/24°C, Water Temperature (Entry/Exit): 12/7°C |
|||||
Cooling Capacity Range |
kW |
1.20~5.72 |
3.60~10.50 |
3.60~10.50 |
4.20~15.00 |
4.20~15.00 |
Cooling Power Input Range |
kW |
0.65~2.40 |
1.12~4.47 |
1.12~4.47 |
1.80~7.30 |
1.80~7.30 |
Cooling Current Input Range |
A |
2.9~10.5 |
4.9~19.6 |
2.0~7.9 |
7.9~32.1 |
3.2~12.9 |
Hot Water Condition |
Ambient Temperature (T/F): 20/15°C, Water Temperature (Entry/Exit): 15/55°C |
|||||
Hot Water Capacity Range |
kW |
3.92~10.68 |
6.50~18.50 |
6.50~18.50 |
10.00~27.00 |
10.00~27.00 |
Hot Water Power Input Range |
kW |
0.78~2.47 |
1.27~4.65 |
1.27~4.65 |
1.90~7.10 |
1.90~7.10 |
Hot Water Current Input Range |
A |
3.4~10.8 |
5.6~20.4 |
2.4~8.21 |
8.3~31.2 |
3.4~12.5 |
Additional Information |
||||||
Max. Power Input |
kW |
3 |
5,3 |
5,3 |
7,5 |
9 |
Max. Current Input |
A |
13,5 |
24,5 |
10,5 |
35 |
15,8 |
Water Flow |
m3/h |
1 |
1,7 |
1,7 |
2,9 |
2,9 |
Refrigerant / Proper Input |
kg |
R290 /0.50kg |
R290 / 0.85kg |
R290 / 0.85kg |
R290 / 1.30kg |
R290 / 1.30kg |
CO2-Equivalent |
t |
0,0015 |
0,0026 |
0,0026 |
0,0039 |
0,0039 |
Sound Pressure(1m) |
dB(A) |
43 |
43 |
44 |
47 |
47 |
Sound Power Level (EN12102) |
dB |
57 |
57 |
58 |
62 |
62 |
ErP Level (35°C) |
ErP |
A+++ |
A+++ |
A+++ |
A+++ |
A+++ |
ErP Level (55°C) |
ErP |
A+++ |
A+++ |
A+++ |
A+++ |
A+++ |
Net Weight |
kg |
80 |
160 |
160 |
202 |
202 |
Operation Pressure (Low Side) |
MPa |
0,8 |
0,8 |
0,8 |
0,8 |
0,8 |
Operation Pressure (High Side) |
MPa |
3 |
3 |
3 |
3 |
3 |
Unit Dimension (L x W x H) |
mm |
1167x407x795 |
1287x458x928 |
1287x458x928 |
1250x540x1330 |
1250x540x1330 |
Shipping Dimension (L x W x H) |
mm |
1300x485x940 |
1420x540x1080 |
1420x540x1080 |
1380x570x1480 |
1380x570x1480 |
Compressor |
Brand |
HIGHLY |
HIGHLY |
HIGHLY |
HIGHLY |
HIGHLY |
Compressor Technology |
Full DC Inverter |
Full DC Inverter |
Full DC Inverter |
Full DC Inverter |
Full DC Inverter |
|
Circulating Pump |
Brand |
Grundfos |
Grundfos |
Grundfos |
Grundfos |
Grundfos |
Operating Ambient Temperature |
C° |
-25 ~ 43 |
-25 ~ 43 |
-25 ~ 43 |
-25 ~ 43 |
-25 ~ 43 |
Fan Quantity |
/ |
1 |
1 |
1 |
2 |
2 |
Fan Motor Type |
/ |
DC motor |
DC motor |
DC motor |
DC motor |
DC motor |
Fan Power Consumption (Min~Max) |
W |
55~105 |
60~120 |
60~120 |
60~160 |
60~160 |
Fan Speed (U/min) |
RPM |
300~600 |
220~600 |
220~600 |
300~750 |
300~750 |
Water Connection (inch) |
inch |
1 |
1 |
1 |
1 |
1 |
Water Pressure Drop (max) |
kPa |
40 |
20 |
20 |
65 |
65 |
Circulation Pump Head |
m |
7,5 |
7,5 |
7,5 |
12,5 |
12,5 |
Cabinet Type |
/ |
Galvanized sheet+ASA |
Galvanized sheet+ASA |
Galvanized sheet+ASA |
Galvanized sheet+ASA |
Galvanized sheet+ASA |